Over the course of 2 years Shepherds worked with SBG to construct and integrate a major upgrade to Ward 14 a/b.
SCOPE OF WORK
- New switchboards with ComAP control and ATS changeover for Essential & Non Essential power
- New Communications room Switchboards, Essential & non Essential power
- New Essential and Non Essential circuit breakers & submains from Main switchboards
- Electrical and Communications cable trays
- New Medical panels and body protect certification for patient areas
- New LED Lighting and Dali Lighting control
- Witness testing of componentry with Independent Commissioning Agent.
LIGHTING
Lighting control installed was designed, engineered, tested and commissioned by our in-house engineers, the lighting control allows control of patient rooms by 2 or more switches and the nurse call controller, the patient room lighting is controlled by a switch and absence sensor, this sensor turns off the light if a patient forgets to turn off light.
Presence detection is also set up in other non patient or staff area’s. The Hallways of the wards are controlled by a programmable touch screen located near the Nurses station so the lighting is able to be dimmed or turned off to suit the time of day.
The Emergency/Exit Lighting is also connected to the Dali system and is connected to the Hospital communications network, the testing of this system can be operated remotely from the build and test results are stared on the head end PC.
All patient locations are ‘Body Protect’ areas and have recessed Medical service panels that house essential/non essential power, communications outlets, medical gasses and nurse call design of these panels required coordination and input from the various trades and end users.